Code 81-14 VFD System Fault – Unbalanced PFCM Code 81-54 VFD System Lockout – Unbalance PFCM

Fault codes covered

81-14, 81-54

Applicable to 4 and 5 ton models only with multiple reactors. This fault occurs when current in PFCM circuits is not balanced. It is most likely caused by a disconnected or faulty reactor. The VFD will shut down and attempt to restart after each occurrence of code 81-14. After 2 occurrences within 10 minutes, code 81-54 is set and system is locked out for 4 hours.

Disconnect and measure resistance of both reactors in system. As reactor charges the resistance will be reduced to 0. If measurement is open, replace reactor. Otherwise replace VFD.


Source: ACHPVSR454-02SM troubleshooting pages.